AC source power & DC source power manufacturing factory

Calculating method of alarm current

As we all know, the capacity selection of AC power supply equipment is very important.choosing the right AC power supply is very important for production, manufacturing, testing and R&D!

excessive capacity selection will increase unnecessary property investment; too small capacity selection will affect the normal production, testing and R&D process and even lead to unusable.

therefore, mastering and understanding the calculation of alarm current will clearly know how to choose the capacity of AC power supply equipment. Suitable power supply equipment will make people feel like a tiger!

AC power supply is divided into single-phase power supply and three-phase power supply according to the different output power.therefore, the calculation method of alarm current can also be divided into two kinds: single-phase power supply and three-phase power supply.
the following are introduced separately:

One:Single-phase power supply
Output 0-300V: divided into low and high gear.the alarm current of low-voltage gear is 120 V, and that of high-voltage gear is 240V. capacity (VA)/gear voltage (V)=gear alarm current (A).

Take 5KVA power supply as an example: 5000VA (capacity)/120V (low grade)≈42A; 5000VA/240V (high grade)≈21A.so we get the alarm current: the output of 5KVA power supply is in the range of 0 -150V, the maximum alarm (limit) current is 42A; the output of 5KVA power supply is in the range of 0 -300V, and the maximum alarm (limit) current is 21A.

Output 0-600V, low-grade 240V, high-grade 480V, the same method to get the alarm current of 21/10.5A.
The simple method is that we only need to calculate the low-grade or high-grade alarm current. Another kind of alarm current can be obtained immediately according to the low-grade alarm current = 2 times the high-grade alarm current

Two: Three-phase power supply
The alarm current is a single-phase alarm current, so the three-phase power supply needs capacity/3 to get the single-phase capacity, and then according to the calculation method of the alarm current of the single-phase power supply, the alarm current of the three-phase power supply can be obtained.

Take three-phase 15KVA power supply as an example: 15KVA/3 = 5KVA, 5000VA/120V≈42A (low-grade alarm current), 42A/2 ≈21A (high-grade alarm current).therefore, the alarm current of three-phase 15KVA power supply is 42/21A.

It is not difficult to find that the calculation of alarm current focuses on the unit of capacity is VA, the unit of voltage is V, and the unit of alarm current is A. Therefore, if the known unit of capacity is KVA, the unit of KVA should be converted to VA when calculating the alarm current. 1KVA is 1000VA.
Recommend Products
Online service
Service Hotline
86-769-89616802
86-13602353727

ADMIRE POWER
主站蜘蛛池模板: 老子影院午夜 | 羞羞的视频在线观看 | 一区欧美| 久久精品国产2020观看福利色 | 中文字幕日韩欧美一区二区三区 | 国产午夜亚洲精品国产 | 看全大色黄大色黄大片一级爽 | 国产乱码精品一区二区三区卡 | 日韩 欧美 亚洲国产 | 99j久久精品久久久久久 | 99视频精品全部国产盗摄视频 | 日韩视频免费在线播放 | 亚洲精品在线免费 | 午夜色网站| 久久99这里只有精品国产 | 欧美三级aaa | 久草狼人 | 999久久久精品视频在线观看 | 色老头老太做爰视频在线观看 | 亚洲精品国产suv一区88 | 在线视频精品一区 | 99爱视频在线观看免费播放 | 亚洲swag精品自拍一区 | 久久久久久国产精品免费 | 亚洲图片综合区 | 亚洲精品久久99久久 | 性欧美videos高清喷水 | 天天干天天综合 | 男人爱看的网站 | 无遮挡又黄又爽又色的视频免费 | 国产精品久久精品福利网站 | 激情五月开心婷婷 | 婷婷免费高清视频在线观看 | freexxxx性特大另类ww | 一级黄色网 | 玖玖国产在线 | 色综合天天综合网看在线影院 | 日本一级欧美一级中文 | 99精品一区二区三区 | 欧美亚洲国产精品久久久久 | 不卡一区二区在线 |